Checked operation of system. Return air 73DB, supply air 53DB, temperature drop is 20 degrees at 63%RH. Static pressure is -.10 in the return, +.05 in the supply. Air circulation system is drawing 1.3 amps and the voltage enhancement system is within specifications with a reading of 10.2. Heat transfer media is clean. Outdoor heat transfer media is clean. Air exhaust system is working properly and drawing.6 amps. Refrigerant pumping system is working properly, drawing 6.4 amps, system pressure is 116/299psig at 82 degrees SH 11, SC 9. Voltage enhancement system is within specifications with a reading of 34.1/5.01.