1638 Elkton Road
Elkton, MD 21921
410-392-9350

Job Locations
for edgewood, md


Map of Edgewood MD
howardmjr22@gmail.com

howardmjr22@gmail.com


Job Checkin

Voltage enhancement system factory specs 15uf actual 11uf is below factory specs recommend replacing. Air movement system blower wheel needs to be cleaned. Indoor air movement system factory specs 1.4amps actual 1.18amps. Found outdoor service disconnect has corrosion. This will cause poor connection to the outdoor unit. Causing start-up issues for refrigerant pumping system as well as higher amp draws recommend replacing. Outdoor voltage enhancement system factory specs 35/5 actual is 33/4 recommend replacing as it is close to being out of factory specs and range of operation. Refrigerant Pumping System RLA factory specs 10.7amps actual 5.79amps, Outdoor air movement system factory specs .80amps actual .60amps Delta T 23 degrees. Checked all electrical wiring connectors and harness are tight and secured