Heat pump inspection. Heat transfer media coil system is good. Air movement system blower is clean. Indoor voltage enhancement system factory specs 15uf actual 14.70uf. Replaced media air filter 20X25X4 supplied by customer. Delta T 21 degrees. Air movement system factory specs 3.1 amps actual 3.1. All electrical connections are tight. Outdoor voltage enhancement system factory specs 45/5 actual 45/4.89 Refrigerant Pumping System RLA 16.7amps actual 7.10amps. Air movement system factory specs .97amps actual .81. coil is clean all electrical connections and harness are tight and secured system is operating as intended at this time