1638 Elkton Road
Elkton, MD 21921
410-392-9350

Job Locations
for havre de grace, md


Map of Havre de Grace MD
howardmjr22@gmail.com

howardmjr22@gmail.com


Job Checkin

Performed club rejuvenation ac cleaning. Refrigerant Pumping System RLA factory specs 12.8 amps actual 4.05 amps. Air movement system factory specs 0.95 amps actual 1.06 amps. Voltage enhancement system factory specs 40/5uf actual 38/4.88uf tighten spade connectors, voltage gateway res 18.1. Cleaned condenser coil. Checked all electrical wiring connectors and harness are tight and secured Delta T 22 degrees. Indoor air movement system factory specs 8.7 amps actual 4.75 amps. Indoor voltage enhancement system factory 10uf actual 9.9uf. Air movement blower wheel is clean free of any obstruction. Heat transfer media coil system is good and clean. Checked all electrical wiring connectors and harness are tight and secured system is functioning as intended at this time.