club rejuvenation: Heat rise was 65. Air filter system was clean and recently changed out by customer. Air movement system was clean and clear of all debris and signs of concern. All wiring was clean and secure. Drain line system was clean and clear. Cleaned off inside and outside of indoor unit with proper cleaner and wipes. Outdoor voltage enhancement system was running at 69.5uf. Factory spec is a 70uf. Voltage gateway system was clean and clear of all debris and signs of concern. Cleaned off inside and outside of outdoor unit with proper cleaner and wipes. System was up and running at normal operation at the end of the visit.