Club AC cleaning: delta T is 14 degrees. Air filter dirty. Customer will replace filter. Indoor fan is clean. Indoor fan amps 5.3. Leak searched indoor and outdoor coils and found no leaks. Outdoor RLA rated 17.1 amps actual is 9.3. Outdoor FLA amps rated 1.7 actual is 1.1. Outdoor voltage enhancement system rated 45/10mfd actual is 41.5/9.1. Voltage enhancement system is out of factory spec. Recommend replacing voltage enhancement system.