In Mesa, AZ: DIAGNOSTIC- On arrival, found compressor not running. Checked run capacitor and found 1.1/5.8/440; should be at 40/5/440. Talked to customer about replacing capacitor and adding a hard start kit. Customer approved the 40/5/440 capacitor and declined the hard start kit. Installed new capacitor and cycled system on. Upon departure, system is running properly and within manufacturer specifications. Service complete. Return 91/Supply 71.