In Queen Creek, AZ: DIAGNOSTIC- On arrival, found system running. Customer had system set for 77 degrees. Checked splits: Return 77/Supply 58. Checked Freon levels. Suction 125/Liquid 350. Checked volt and amp draws. Compressor: Rated at 17.9/Actual 13.76. Outdoor fan motor Rated 1.1/Actual .92. Found contactor very burnt and pitted; hard start kit is at 0.0 MFD Rated at 189-227. Need new single pole contactor and new hard start kit. Installed parts. System is running properly. Checked attic furnace and duct work looks good. No other issues found. Service complete.