Performed 189.00 HVAC tuneup. Thermostat ok, set to ‘cool’ and inspected a/c unit. Ambient air temp 67*F, coil ok, compressor/fan motor RLA/FLA 8.6/.7, dual capacitor values 41.4/4.8uf, down from 45/5uf, contactor & wiring ok, refrigerant (R22) suction/discharge psi 52.7/127.2, SLT/LLT 60.8/71.7, VSAT/LSAT 28.1/72.7. Furnace ducts & filter ok, blower assembly ok, motor FLA 7.2, controls & wiring ok, flushed condensate drain line/pump, supply/return air temps 51/69*F(18*F diff). Advised customer of findings and discussed Priority Club membership benefits. Customer signed up for HSP and will contact MPHC & E for dual cap replacement at a later date. Overall system conditions are good.