Found system low on refrigerant 410A. Performed a electronic leak detection test. Found leaks at the low side service valve and at the piston coupler. Replaced the valves cores and caps. Was able to secure the piston fitting. Retested for leaks. All checks ok. 133/390 psig. 18.8 SH, 13.5 SC.