MY PLUMBER HEATING COOLING & ELECTRICAL
MANASSAS, VA 20109
800-280-2820

Job Locations
for broad run, va


Map of Broad Run VA
CRAIG M.

CRAIG M.


Job Checkin

Unit 1 attic Filter homeowner will replace Condensation line good Blower wheel needs cleaning Blower motor capacitor 12.9 Blower 1.2 Outdoor coil needs cleaning Compressor 6.2 Fan .7 Capacitor 36/5 Contactor operational Running pressures R22 63 saturated temp 36.6 282 saturated temp 126 Basement unit Supply 51 Return 73 Filter replaced with customer supplied Condensation line good Blower wheel ok condition Blower motor capacitor 12.5 Blower motor 1.3 Outdoor coil needs cleaning Compressor 6. Fan.8 Contactor operational Capacitor Running pressures 410a 133.3 saturated temp 37.7 292.4 saturated temp 94 Clean out coils after homeowner approval Thank you for your business Have a great mother’s day