SOLD FIL001.... Performed hsphvac maintenance on a 2011 ICP heatpump system. Installed a new air scrubber air purification system. Cust had a duct cleaning company that discussed several issues with Mr. Pelano. Microbial growth found in the air handler. Discussed the replacement of the bypass humidifier. Turned off for the season. Mr. Pelano wanted me to price and email info for the ductwork and the humidifier replacement. Moved the air filter from the return box to the EAC chassis. Prefilters ok. Cells are no longer in the EAC. Wireless control system tested ok. Zone damper operating ok. Discussed additional zoning or volume damper installation for better conditioning of the air on all three levels. Acoil is rusted and dirty. Condenser coil ok. Zoning system tested ok. Scrubber fused through the a/h control board. Taped the return box to the a/h and covered the filter slot. A/H 246v. 27 low voltage. 4.3 fla. Blower wheel dirty. Heatpump- 247v. 9.2 fla. #8 wiring to the disconnect and