Upon arrival recovered R-410 freon from the new installed heat pump system and removed factory DEFECTIVE high pressure switch. Installed new high pressure switch in place, replaced the bi-flow filter and recharged 6lbs. of R-410 freon in the new installed heat pump system. Checked operations, unit is working and cooling properly at this time.