1903221809JBB...1903221809JBB... Arrived to complaint of water coil solenoid not activating when called for. Found that system was wired incorrectly. Found wiring for solenoid on y1 and c terminal at furnace board. Wired to y/y2 and c and tested operation. Solenoid opens and closes now when called for. System back on line at this time.