Basement Supply 55 Return 73 Filter good condition Blower wheel needs cleaning Blower motor capacitor 7 rated for 7.5 Blower motor 1.2 Outdoor coil cleaned Compressor 5.2 Fan.7 Contactor operational Capacitor Running pressures 278 saturated temp 90.8 line temp 83.8 130 saturated temp 45 line temp 55 Superheat 11 Subcool 7 Attic Supply 53 Return 74 Filter good Condensation line good Blower wheel ok condition Blower motor.7 Cleaned out unit Compressor 3.1 Fan.3 Contactor operational Capacitor 24/3.7 rated for a 30/5 Running pressures 410a 127 saturated temp 44 line temp 57 278 saturated temp 91 line temp 89 Subcool 2 Superheat 13 Talked with homeowner regarding replacement of capacitor and cleaning blower wheel for basement unit Declined due to fact homeowner has home warranty (homeowner don’t live there yet moving in Monday) No lose or damage wiring