I completed diagnostics and found the issue to a bad transformer. Transformer receiving 120 from the board but not putting out 24v. I replaced transformer and still having the same issue. I found that the white neutral wire was getting 60v. Neutral wire getting charged. Customer had some 12/2 wire and I ran new wire. Verified wiring to the board. I turned the system on and still no 24 to the board. Verified 120 to the furnace. No power to the neutral wire. Verified 120 to the transformer. I verified 24 from the transformer. The board not receiving the 24v. Bad board as well.