Completed restriction repair for AC system on the second floor. Replaced expansion valve on indoor unit. Blew nitrogen through both sides of system. Pressure tested to factory specification of 150 psi for 30 minutes. Evacuated to 529 microns. Charged system with 8 pounds of virgin R22. System now running 55/155 with SH 17 and SC 9.