R410a adjustment Dual capacitor turbo 200 Arrived at clients for two system cooling maintenance. Set thermostat to cooling. Flushed condensate drain line. Inspected blower wheel and coil. Checked electrical components. Changed air filter for client. Checked downstairs furnace. Inspected blower wheel and duct work. Checked electrical components. There was no filter inside cabinet. Washed both outdoor coils. Checked electrical components for both systems. Capacitor was very weak for lower level system. Client approved replacement. Checked both systems refrigerant levels. Lower level system was low on refrigerant. Client approved refrigerant recharge. Systems are operational at this time. Job complete.