Service call. On arrival I found the well pump pulling 58 amps and 20amp single pole breakers tripping after a few seconds. The pump is 230vac and wired to two breakers, after removing the neutral from the second breaker and placing on the neutral bar the circuit drew 11.3 amps and did not trip. The water is currently running.