Upon arrival the customer stated the furnace would light then immediately shut off. I cycled furnace and found flame sensor reading 0.0uA. I pulled and cleaned sensor then reinstalled. After cleaning read 2.6uA. I allowed to run approximately 15 minutes with no further issues. At time of departure furnace operational with a temp rise of 50 degrees. Goodman