Alexandra  C.

Alexandra C.


Job Checkin

Checked in with Customers. Set up my equipment. Cleaned out control cabinet. Tested the 45/5 dual run cap. ( in factory range). Pulled amp draws . Comp - 14.1 LRA / 7.41 A. ODF - .85A IDB - 2.51A Sub- Cooling 7.56°. @ 8:15am Super- Heat. 5.6° Discharge 110 Suction. 39.6 Washed Condenser coil. Left 20x30x1 standard filter in the open garage The unit is operating at factory recommended specifications at this time.