Picked up filters . Checked in with Michael . Replaced return filter . Inspected Thermostat. Climbed up to attic . Removed and washed air purifier filters . Dried out filters prior to setting back into place Tested 45/5 dual run capacitor. Pulled amp draws . Checked refrigerant charge (410A) Suction psi - 105 / 20.6 ° SH. High Side. 176.5/ 7.1° Sub-Colling Washed Condenser coils . The system is operating at factory recommended specifications .