Contacted resident Left filter with resident Went to roof Cleaned electric compartment Checked all wiring, good Checked temperature split Supply air 42 Return air 61 Split of 19,good Compressor amps 8.4 rated 15.4 Condenser amps 1.0 rated 1.2 Dual cap 50+5 Herm 48.4, good Fan 5, good Unit running as per manufacturer's specifications