2x Ac tune ups. Added algae tabs to drain lines,Filters okay. Indoor coils okay. Thermostats within 1°F. Cleaned outdoor ac coils. Tested left side Kitchen system, System needs 1-2 lbs R410a freon. Outdoor fan motor starting to run slightly higher amps. Be aware this may fail in the future. All other mechanical components within their normal ranges. Tested right side master bedroom system. Readings indicate freon is perfect. Start capacitor right on verge of needing replaced, price provided. All other mechanical components within their normal ranges.