Ac repair: common line from capacitor to contactor was charred and severed from the capacitor. Capacitor was burned and damaged. Recommend replacing unit due to age. Replaced common wire to contactor and replaced capacitor for the compressor. System is cooling with a 17 degree the.perature split. Compressor amp draws and ohm readings are in range.