Matthew J.


Job Checkin

Maintenance: unit was functioning properly and producing a 20 degree split. Compressor and fan motor amps were in range along with the capacitor. Pressures were in range as well with a 8 subcool. Indoor unit amp draws were in range. It is ECM blower so no capacitor. Coil is sitting on foam to increase pitch of draining due to bent cabinet was causing some water to drip on to unit.