Service call on 08/13/19 On arrival set units to call for cooling checked condenser unit outdoor found error codes on comfort alert #1 long running compressor checked electrical connections checked voltage and amps checked compressor capacitor checked coil reset the unit from mean breaker tested checked amps for compressor checked pressure and temp and they are ideal indicating zero leaks measured subcooling and superheat measured supply and return air temp stayed for 30 minutes unit operating normal at this time. Collected $105.40 for diagnostic fee and $50.15 for dispatch fee total $155.55 On C.C