4401 Eastern Ave #17
Baltimore, MD 21224
410 781-1002

Job Locations
for belcamp, md


Map of Belcamp MD
Youssef  D.

Youssef D.


Job Checkin

Upon arrival system off, turned on to test, found 10 degree split across indoor coil and 15 on outdoor coil. Attached gauges, found system operating at 315 high and 130 low. System had 5 degrees subcool and 40 degrees super heat. Suspect system low on charge but unable to confirm. Found dirty filter and replaced, filter needed to be changed but do not think main contributing factor.