4401 Eastern Ave #17
Baltimore, MD 21224
410 781-1002

Job Locations
for damascus, md


Map of Damascus MD
Christopher A.

Christopher A.


Job Checkin

Customer replaced the dual run capacitor and installed a hard soft by themselves. These were repairs recommended last heating check up. The drain line did drain but the unit does not have any form of safety device to prevent flooding in the event the drain backs up. I recommended EZ Trap. I checked the electrical wiring and electrical systems, all are within specification. I operated the unit on cooling mode. The unit uses a fixed orifice metering device. As the unit ran longer the superheat started to approach 20 degrees and subcooling never went above 3-4 degrees. Unit is cooling with 20+ degree delta temperatures across the evaporator coil but there has been a loss of refrigerant that will only get worse with time. I recommended doing an electronic leak search and gave them customer several estimates depending on the results of the leak search. Customer does not want to move forward with any repairs at this time and is still not interested in becoming a member.