4401 Eastern Ave #17
Baltimore, MD 21224
410 781-1002

Job Locations
for gambrills, md


Map of Gambrills MD
Youssef  D.

Youssef D.


Job Checkin

Upon arrival found indoor unit running but putting out 80 degree air. Refrigerant flowing through line set but liquid line very hot to the touch. Inspected outdoor unit and found condenser fan motor not running and compressor short cylcing on high pressure. Disconnected power and checked run capacitor, found capacitor at rating for compressor but failed for fan motor. Tried replacing capacitor and fan motor running normal now. Normal amp draws on fan motor and compressor. Indoor unit now operating with 18 degree split on air temps, 80 return air and 62 supply air. System cooling properly. Property management authorized work to be preformed with total of $350.