Replace condenser fan motor, blade, and capacitor. Found unit had a blown fuse. Went out with the maintenance supervisor to pick up 4 fuses. Replaced the fuse. Turned the unit back on and the fuse blew again. Went through to every part on the circuit to find what was making the fuse blow. Found that the condenser fan motor was grounded. Ordered and picked up the materials for the job. Installed the new factory motor, blade and capacitor. Made all wiring connections. Started the unit. Found 1st stage compressor not wired up. Checked the compressor and the circuit has no refrigerate in it. Also found the wiring for the heat and the gas line has been shut off. Unit is R22 refrigerate and will no longer be available next year. Unit should be changed out to a R410A system. Only circuit 2 is running in A/C mode at this time.