Up on arrival Replaced condenser fan motor with blade, contactor. Cleaned condenser coil. Tested system for operation found that system would run for 10 minutes and cut off . Went to air handler and found clogged up air filter and weak voltage absorption rated 10uf actual readings 5.6uf . Customer approved to replace voltage absorption at the blower motor. Cleaned air filter and replaced voltage absorption. Tested systems. System operating normal at this time. Voltage absorption 10uf