4401 Eastern Ave #17
Baltimore, MD 21224
410 781-1002

Local Reviews
for upperco, md

Rated 1.0 out of 5 stars based on 1 customer reviews

RIP OFF!!!!

$550.00 for 2 lbs of Freon....

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for upperco, md

Saber Z.

Saber Z. Job Checkin

Nearby Now


youssefd@supremeservicetoday.com

youssefd@supremeservicetoday.com Job Checkin

Nearby Now


Colin T.

Colin T. Job Checkin

Replace leaking Evap coil. Confirmed pinhole Leak in middle of coil, oil leaking out. Started by removing refrigerant from system and moving return duct out of the way. Also removed aux heater kit and blower assembly for access to coil. Used copper cutters to cut out old coil, then removed from unit. Put new coil into place then secured. Sanded copper then brazed new coil in. Pressurized system up to 400psi nitrogen and held. No leaks found. Removed nitrogen then vacuumed system down to 400micron and held. While vacuuming I put system back together. Confirmed vacuum held so I added factory charge of 89oz 410a to system. Returned power to unit and ran heat. Checked operation of first and second stage compressor. Monitored refrigerant pressures and temps. Delta air temp is 30degrees across Evap coil. Let system cycle a few times to confirm operation. Unit operating normal at this time.


Christopher  A.

Christopher A. Job Checkin

The air coil is leaking refrigerant. There is oil residue in the condensate pan inside the blower compartment. Customer approved the repair to replace the air coil and filter drier. Unfortunately the unit is out of warranty. I completed a parts order form and a customer follow up form. As a courtesy I charged the unit to hopefully last until the coil arrives. Customer paid $1263.95 today and the same amount due upon the completion of the work.


Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com Job Checkin

Up on arrival performed fall maintenance on 11/18/2019. Changed all filter , checked delta T and P, took readings of all electrical components, checked thermostat for operation, checked unit for operation. Unit working good at this time.


Yonas M.

Yonas M. Job Checkin

Service call 06/22/19 On arrival set unit to call for cooling measured supply and return air temp no DT checked electrical connections checked voltage and amps I checked outdoor ductless heat pump i put my gauge checked pressure and temp I found small non obvious leak the temperature is 27 degrees the pressure 225 I gave quote for customer to checked the leak and repair it but customer agree to add some 410A To the unit I charge the unit 2 pound 410A tested checked the pressure and temp is above 40 degrees stays. tight up all the connections checked electrical connections checked voltage and amps measured supply and return air temp is 25 degrees DT unit operating normal at this time. Collected $457 for charge 410A non obvious leak $89 for dispatch fee total $546 On C.C


Christopher A.

Christopher A. Job Checkin

I replaced the air filter with one provided by the customer. I cleaned the condensate pan and drain lines and ran water to flush the debris and to check for proper drainage without leaks. I checked the electrical wiring and electrical systems, all are within specification. I operated the unit on second stage cooling mode. I recorded 20+ degree delta temperatures across the evaporator coil. I had proper pressure drop across the coaxial water coil. I had normal heat of rejection. Unit operating normal. I recommend adding Intellistart Module to the electrical circuit of the compressor. It allows the compressor to start using 70% less amperage, which helps to prolong the compressors lifespan. Also if the home has backup generators, start assist modules are needed to allow the compressor to start and not overload the generator.