Client called us out today due to no cooling coming from AC. Outdoor condenser is operational upon arrival. Usually an indication of a secondary motor control failing or a refrigerant leak. Found secondary motor control was pulling a 5 out of 45 µF. Client has agreed to move forward with replacing failed component. Replaced component and cycled system. Did not have standard component, so upgraded client to turbo at the price of the standard. System is now operational and cooling the home. Getting a 15 to 16° split. Recommend hard start kit in off-season to mitigate compressors workload and extend systems lifespan. Thank you for trusting Thompson with your heating, cooling and plumbing needs.