Client called us out today due to system not properly cooling master bedroom. Another tech had been out earlier this week and was able to get the system to work for a few days. Outdoor condenser is operational but no cooling is taking place. Secondary motor control for compressor is within spec pulling a 67 out of 70 µF. Hooked up refrigerant gauges and found compressor was completely stagnant with no push to pull. This would indicate the compressor is the issue and would need to be replaced. Client stated Maytag system had refrigerant leak issues in the past. Due to the state and age of the system and what would be required for repairs advised client replace with more reliable model. Client has agreed to move forward with system replacement. Will bring out portable cooler tomorrow. Install date scheduled for August 1st. Thank you for trusting Thompson with your heating, cooling and plumbing needs.