Came out for thermostat not working. Also while is was here performed a non msc ac tune up. Found the evaporator coil needed to be cleaned and the blower also needed to be cleaned. Today I cleaned the coil and replaced the thermostat. Found the LRA is high on compressor and the blower motor is showing signs of age. Furnace is a 2011 Goodman. Capacitor is testing right on the edge of bad. It is still working today. Found the static pressure is high in the blower due to 1” filter. All other electrical components are testing properly and working properly. See health report card. I installed a luxpro instead of the Aprilaire thermostat per Raymond. Warehouse team had to bring me this thermostat. Everything was working properly when I left the call.