I completed diagnostics and found the condenser not working. Not cooling. The fan was working on the condenser. I pulled disconnect and checked the capacitor. The capacitor had failed. The customer agreed to the repair. After replacing the capacitor system is running properly. Compressor amps-7.8 Fan amps..68 Delta-16 System is now operational and cooling at departure.