CUSTOMER CALLED STATING GENERATOR STARTED DURING AN OUTAGE BUT WOULD NOT TRANSFER - FOUND CONTROLLER IN THE GENERATOR HAS GROUNDED OUT - WIRES 194 & 23 WER NOT GETTING THE CORRECT DC VOLTAGE - REPLACED CONTROLLER - PERFORMED TRANSFER TEST - GEN WORKING NORMALLY AT THIS TIME