13211 Veterans Memorial Hwy.
Douglasville, GA 30134
770-203-0274

Job Locations
for blackshear, ga


Map of Blackshear GA
Tyler L.

Tyler L.


Job Checkin

Starter on generator is to blame for the no start. Service was done at 78.1 hrs based on information on oil filter. Generator has 79.4 hrs currently. After clearing alarm, I hooked up meter to signal wire on starter. Starter received 12v signal but failed to turn over. On the 3rd attempt it started. After it started once it continued to started every time. Starter will need to be replaced to remedy the intermediate no start issue. Customer is going to purchase starter and have us replace it.