GENERATOR FAILED TO EXERCISE. NO ALARMS PRESENT, GENERATOR WAS IN AUTO. WIRE 183 INSIDE GENERATOR WASNT MAKING CONNECTION WITH THE TERMINAL BLOCK. ONCE A GOOD CONNECTION WAS MADE, THE 2 WIRE START WAS TESTED INSIDE THE ATS. GENERATOR STARTED AS IT SHOULD. DISABLED THE EXERCISE FUNCTION FROM THE ATS AND PROGRAMMED THE H PANEL TO PERFORM THE EXERCISE WEEKLY ON WEDNESDAY AT NOON. NO FURTHER ISSUES.
Certified Generac start up. Spoke with owner about not installing the pool equipment close to generator. Generator is working properly.
#2 service. Generator is working properly.
Certified Generac start up. Generator is working properly.
#1 service. Generator is working properly.
GENERATOR FAULTED FOR STUCK THROTTLE. GOVERNOR ACTUATOR WAS FAULTY AND COMPLETELY FROZEN. REPLACED GOVERNOR ACTUATOR AND WAS ABLE TO GET GENERATOR RUNNING. REPAIRS FILED UNDER WARRANTY.
START UP COMPLETE. SEE ATTACHED PICTURES. GAS WORK MAY BECOME AN ISSUE IN THE FUTURE. CUSTOMER IS AWARE.
#1 service. Generator is working properly.
#2 service. Generator is working properly.
#1 service. Did a firmware update and replaced battery. Generator is working properly. If generator faults again for rpm sense loss may need to replace starter.
Battery charger failed and the battery was completely dead. Installed a new battery charger and battery. Tested. Generator is now working properly. Done during #2 service.
#2 service. Generator is working properly.