GENERATOR FAILED TO EXERCISE. NO ALARMS PRESENT, GENERATOR WAS IN AUTO. WIRE 183 INSIDE GENERATOR WASNT MAKING CONNECTION WITH THE TERMINAL BLOCK. ONCE A GOOD CONNECTION WAS MADE, THE 2 WIRE START WAS TESTED INSIDE THE ATS. GENERATOR STARTED AS IT SHOULD. DISABLED THE EXERCISE FUNCTION FROM THE ATS AND PROGRAMMED THE H PANEL TO PERFORM THE EXERCISE WEEKLY ON WEDNESDAY AT NOON. NO FURTHER ISSUES.