First time generator has run in roughly 3 years. Installed new battery. Radiator was 2 gallons low. Hooked up the battery charger and verified it operated. Ran generator several times to monitor for coolant leaks and possible oil leaks. Used the ats to start the generator to test 2 wire start. Generator is producing power(277/480). Customer wishes to perform a test transfer at night very soon.