Sprinkler Inspection Annual Sprinkler Inspection for K building only - 1 wet riser and 4 units Inoperable Deficiency: System is shut off. Will need to investigate as to why it’s shut and will need to air pressure test to see if ok to refill. Water Flow Device is not connected to any alarm nor electric bell. Gauge is dated 2012 and will need To be replaced. Riser is located in rear bedroom closet of apartment 4 in Building K. SYSTEM WILL BE RED TAGGED.