Cody T.

Cody T.


Job Checkin

Sprinkler and Fire Hose Inspection Annual Fire Sprinkler Inspection Annual Hose Station Inspection ***DISPATCH: a service technician will need to be scheduled for this job. DO NOT send the inspector. Inoperable Deficiency: Fire hose valve on dock C, first one is leaking if not tighten will pillars, and water is filled water, recommend to un rack hose and release all water and re rack hose once dry. Need to resolve valve, with a 1 1/12 618R stand pipe fore hose valve Deficiency: All (10) fire hose are due for hydro static testing, shall be replaced and or hydro static tested. No annual sticker was placed inside fire hose cabinet for fire hose inspection. Inoperable Deficiency: Need to trouble shoot why panel goes into alarm, when Panel turns back on. Panel was currently turned off, input fuse and panel went straight to alarm and ground fault on every point, someone disconnected NAC lines Positive leads so NACS will stop going off. Nothing on panel works, nothing will send signal t