Sprinkler Inspection Quarterly Fire Sprinkler Inspection Deficiency for Wet Outside: Riser : - Flow switch housing has broken off screw inside, not allowing another screw to screw into, flow switch should be replaced. Potter VSR-F, 2inch riser. - Recommend to add lock and chain to control valve on riser. - Need to add a Calc Card to riser. -Need to add lock and chain to back flow with a address sign. Suggested for Wet Outside: Suggest to replace gauge, MFG date 2013, as it is is the end of the month and will have to changed out next year shall be replace this year with other deficiencies