Pressure Reducing Valve Installation: The client reported banging pipes whenever multiple fixtures ran at once. My gauge reading showed 110 psi static pressure from the main. I installed a brass PRV set to 65 psi, added a thermal expansion tank at the water heater, and rechecked system pressure, eliminating water hammer and protecting downstream fixtures.