The unit was at 45 degrees and the staff said they had adjusted the stat multiple times because it was above 50 degrees. I pulled the unit out and removed the back and the condenser was plugged. I brushed and cleaned it with dirt blaster They ran the unit and adjusted it multiple times to get it to shut off at 34 degrees. I told the staff to let it run for a day and check temp before putting product back in.