Arrived on, 8/21/23- Tim While on site Ken Kade asked to have the a/c in the good spirit cafe checked out as it was leaking water. Found unit way out of level and no p trap on the condensate line. Propped up unit and adjusted the all thread to level the unit. Cut in a new customer supplied p trap and also found the panels were not sealed, screwed in the front panels and started unit. Checked for leaks and unit is no longer leaking at this time.