Response from Chud Air Conditioning & Heating:
Joe, thank you for leaving Chud a 5 star review!
Response from Chud Air Conditioning & Heating:
The team here at Chud loves to see 5 star reviews! Thank you Joe.
Manufacturer Ncp Model # NCPC-024-3010 Serial # 24714165 Completed a preventative maintenance. I changed the 18x18x1 filter, I also added evaporator coil water treatment tablets on the evaporator coil pan. I also made sure the system is draining properly. The temperature split was 16 degrees.Then I performed a amperage readings on the compressor and condenser fan motor both are operating high. The compressor is rated for 8 running at 9.8 and the fan motor is running at 1.3 and rated for 1.2. Also, the thermostat button were hard to operate but the customer did not want to replace it. The unit is very old and should be replaced in the near future
Gave estimate to customer to replace a dryer vent booster fan that was damaged by another dryer vent cleaning company.
Replaced hot water heater with 30 gallon Bradford white HWH. Adapted to existing connections and bled air from all water lines. Cycled and tested, system working properly at this time.
Performed preventative maintenance for a carrier heat pump. Serial #2514A68878 model #FB4CNF018. Upon arrival I powered the system down and removed the access panels. The evaporator coil’s are dirty and should be cleaned (see photos). The homeowner is currently re renovating the home and there is construction going on. Checked all electrical connections to ensure that they are secure and in good condition. The heat kit coils are in good condition. Tested the drain pan and drain line with several bottles of water to ensure that there are no leaks or clogs. I re attached the access panels and called for heat. I observed the system starting normally. The supply temp is at 121°F. I went on the roof to inspect the heat pump. The condenser coils are clean and in good condition. All electrical connections are secure and in good condition. The condenser amp draws are 4.7 for the compressor and .32 for the fan. The heat for the system is operating properly at this time. I powered the system do
30 gal water heater customer opted not to change expansion tank
Performed air duct cleaning and sanitation on a 2 bedroom single system house. All vents and ductwork are clear of dust and debris at this time. System is functioning properly at this time. Recommend duct cleaning every 3-4 years. Thank you for your business! Customer paid in advance.
Performed preventative maintenance for gas furnace. Customer mentioned the system not maintaining set temperature all the time. Inspected all the electrical components. Confirmed proper high and low voltages. Replaced the air filter due to the customer installed filter that while it was new was way too restrictive for this system. Heat was exceeding 200°F which is over the max design temperature. Once I installed our 16x25x1 air filter the system maintained standard system supply temperature of 136°. Inspected gas piping for any leaks. Tested the blower and inducer amp draw. Both were operating within manufacturer specs. Performed a combustion analysis on the furnace. System is operating at 80.4% efficiency with a CO level of 16ppm. Cleaned the burners, flame sensor and burner compartment. Flame sensor was also very dark from carbon. If problem happens again it could be flame sensor. In my opinion it was over heating due to new filter too restrictive though. System is operating properl
Performed rooftop dryer vent cleaning from inside using brushes. Dryer vent, Duct, flex hose ,lint trap and rear of dryer are all clear of lint and debris at this time. Dryer is functioning properly at this time. Recommend dryer vent cleaning every 1-2 years. Thank you for your business!
Performed preventative maintenance for a carrier furnace. I observed the system starting normally. The supply temp is at 128°F. The blower motor amp draw is within normal range. I observed the system shut down normally. Checked all electrical components needed for heating. Evaporator coil is clean. Drain line is clear of clogs. Replaced the air filter size 14x20x1. Condenser coil's are clean. Amp draws are 5.6 for the compressor and .3 for the fan. Refrigerant pressures are within normal range for the outdoor temperature. The system is operating properly at this time.
Attempted to perform preventative maintenance on Carrier Heat Pump. Outside unit is on the roof for this apartment/condo complex. PA talked to homeowner on rescheduling the maintenance due to not having an extension ladder to complete the Maintenance. System has a 14x20x1 air filter that will need to be replaced on the rescheduled visit as well. PA will contact office on rescheduling this maintenance appointment and more details.