Job Checkin

Arrived onsite to customer having issue with furnace CPI had recently had swapped out a capacitor on blower assembly. Customer stated that error code had returned stating a main limit was present. Customers furnace was actually throwing an error code indicating a bad inducer motor/ pressure switch. Tested blower capacitor and found it to be well within tolerance and functioning as designed. Inducer motor appeared to be locked up. Informed customer of findings and informed her it was not related to previous work. Offered diagnostic to be able to pinpoint issue. Found system was receiving correct voltage from control board but was pulling over double the amount of amps it should. Spun inducer motor and it slowly began to pick up speed and function. Customer informed me she had smelled a very burnt motor like smell coming from unit in previous days. Customer will need to swap out inducer motor housing and capacitor. Informed customer no warranty or guarantee would be provi